ISO 16358-3-2013 pdf free download.Air-cooled air conditioners and air- to-air heat pumps Testing and
calculating methods for seasonal performance factors Part 3:Annual performance factor
Climatiseurs a con denseur a air et porn pes a chaleur air/air — Essais et méthodes de calcul des coefficients de performance saisonniers — Partie 3: Coefficient de performance annuel (COPA).
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are Indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
Iso 5151, Non-ducted air conditioners and heat pumps — Testing and rating for performance
Iso 13253, Ducted air-conditioners and air-to-air heat pumps — Testing and rating for performance
ISO 15042, Multiplesplit-system air-conditionersand air-to-airheat pumps — Testing andratingforperjórmance ISO 16358-1, Air-cooled air conditioners and air-to-air heat pumps — Testing and calculating methods for seasonal performance factors — Part 1: Cooling seasonal performance factor
ISO 16358-2, Air-cooled air conditioners and air-to-air heat pumps — Testing and calculating methods for seasonal performance factors — Part 2: Heating seasonal performance factor
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 5151, ISO 13253, ISO 15042 and the following apply.
3,1
cooling seasonal total load
CSTL
total annual amount of heat that is removed from the indoor air when the equipment is operated for cooling in active mode
3.2
cooling seasonal energy consumption
CSEC
total annual amount of energy consumed by the equipment when it is operated for cooling in active mode
3.3
cooling seasonal performance factor
CSPF
ratio of the total annual amount of heat that the equipment can remove from the indoor air when operated for cooling in active mode to the total annual amount of energy consumed by the equipment during the same period
3.4
heating seasonal total load
HSTL
total annual amount of heat, including make-up heat, which is added to the indoor air when the equipment is operated for heating in active mode
3.5
heating seasonal energy consumption
HSEC
total annual amount of energy consumed by the equipment, including make-up heat, when it is operated for heating in active mode
3.6
annual performance factor
APF
ratio of the total annual amount of heat that the equipment can remove from and add to the indoor air when operated for cooling and heating, respectively, in active mode to the total annual amount of energy consumed by the equipment during the same period
3.7
total annual performance factor
TA PF
ratio of the total annual amount of heat that the equipment can remove from and add to the indoor air to the total annual amount of energy consumed by the equipment, including the active, inactive and disconnected modes
3.8
active mode
mode corresponding to the hours with cooling and heating demand of the building and whereby the cooling or heating function of the unit is switched on
3.9
inactive mode
mode corresponding to the hours when the unit is not operating to meet cooling or heating demand.ISO 16358-3-2013 pdf free download.

Download Information
Go To Download

All resources on this website are from the Internet. It is only for personal study and research. No one is allowed to use it for any commercial purpose. If you need, please buy the genuine standard. If there is any infringement of your copyright, please contact the webmaster in time, and I will correct it immediately.