ISO 22968-2010 pdf free download.Forced draught oil burners Braleurs a air souffle pour combustibles liquides.
A safety shut-off device shall be provided between the pump and nozzle as shown in Figures Fl to F.4. It is permissible that the safety shut-off device be integrated with the oil-pump.
In addition, the following applies.
a) Single-stage burners shall be provided with one safety shut-off device in accordance with ISO 23553-1.
b) Two-stage or multi-stage burners shall be fitted with one safety shut-off device for each nozzle. See Figure F.2.
C) Burners with a spill-back nozzle shall be fitted with a safety shut-off device conforming to ISO 23553-1 in both the feed line and return line. A nozzle shut-off valve may be fitted in lieu of the safety shut-off device fitted in the feed line and return line on condition that the nozzle shut-off valve is tested and approved as a safety shut-off device in accordance with ISO 23553-1. See Figures F.3 and F.4.
d) In the case of a burner with a nozzle head it may be necessary to have oil circulation up to the nozzle head, e.g. for pre-heahng purposes. Since there is only a nozzle shut-off device in service, it shall be ensured by a second independent measure that an unsafe fuel discharge is prevented. In the case of a nozzle shut-off device in accordance with ISO 23553-1 a second measure is not necessary. It shall be ensured that the nozzle shut-off device cannot be opened by the return pressure.
5.1 .2.7.3 Burners with a flow rate greater than 30 kg/h
Two series-connected safety shut-off devices shall be provided in the flow line of oil burners with a flow rate
> 30 kgfh. See Figure F.5.
One of the devices shall be of the fast-closing type. The second device may also be used as a final controlling element for the combustion chamber input. Its closing time shall not exceed 5 s.
The following also applies:
a) For burners with a spill-back nozzle, two safety shut-off devices shall be provided in the return line and a pressure monitoring device shall be provided between the power regulator and the safety shut-off device (see Figures F.6 and F.7). A nozzle shut-off valve may replace a safety shut-off device fitted in either the flow line or the return line provided it has been tested and certified as a safety shut-off device in accordance with ISO 23553-1.
Except where a step-regulated burner has a full-load stage, the safety shut-off devices shall be interlocked so that when the flow is open the return is not closed. This can be done, for example by
— making a mechanical connection between the safety shut-off devices in the flow and return (e.g. by means of an actuator), or
— by electric or pneumatic interlocking of the safety shut-off devices in the flow and return lines.ISO 22968-2010 pdf free download.

Download Information
Go To Download

All resources on this website are from the Internet. It is only for personal study and research. No one is allowed to use it for any commercial purpose. If you need, please buy the genuine standard. If there is any infringement of your copyright, please contact the webmaster in time, and I will correct it immediately.