IEC 62109-3-2020 pdf free download.Safety of power converters for use in photovoltaic power systems — Part 3: Particular requirements for electronic devices in combination with photovoltaic elements
Sécurité des convertisseurs de puissance utilisés dans es systèmes photovoltaIques — Partie 3: Exigences particulières pour les dispositifs électroniques combines aux éléments photovoltaIques.
b) PV Module nominal backsheet temperature (TNBS) in degrees Celsius that is used to
calculate the PV module maximum backsheet temperature (TmaxBs) using formula (1) in
4.3.2.1.302. The value used for TNBS shall be either:
1) the PV module Nominal Module Operating Temperature (NMOT) rating,
2) the PV module Nominal Operating Cell Temperature (NOCT) rating,
3) the value of 50 °C, or
4) the value according to the method in Annex A on the actual PV element.
NOTE 1 Some PV modules may have a NOCT rating instead of a NMOT rating. As defined above, either rating can be used to calculate Tmaxs since both ratings are evaluated at 800 W1m2 and an ambient temperature of 20 C. The method used to determine NOCT Is considered to produce a higher value than the NMOT method and represents a more severe test condition.
c) Behind the module air temperature in degrees Celsius will be based on the environmental temperature above and the installation instructions. This temperature shall be the chamber test temperature and is typically greater than the environmental temperature. The following guidance is provided for determining the behind the module air temperature based on the module mounting distance according Figure 302 and Figure 303:
— MIE installed with the entire backsheet exposed to the environmental air temperature and mounted greater than 1 m above the ground or any other surface: environmental temperature or greater;
— Multiple MIE installed greater than 100 mm to 1 m above a surface with no baffling that obstructs air flow: environmental temperature plus 10 °C;
— Multiple MIE installed greater than 50 mm to 100 mm above a surface with no baffling that obstructs air flow: environmental temperature plus 15 °C;
— Other constructions and installation methods that are mounted 50 mm or less to a surface, provided with baffling and/or enclosures shall have a separate evaluation performed before testing the individual module to determine the behind the module air temperature based on the environmental temperature and heating from the MIE under the most severe installation condition according to the installation instructions.IEC 62109-3-2020 pdf free download.

Download Information
Go To Download

All resources on this website are from the Internet. It is only for personal study and research. No one is allowed to use it for any commercial purpose. If you need, please buy the genuine standard. If there is any infringement of your copyright, please contact the webmaster in time, and I will correct it immediately.